The scaling behavior of simulated cooling tower water on a heat transfer surface was investigated. The alkalinity was the main parameter investigated. The fouling vs. time curves were fitted to the equation

  • equation image

which was derived from a simple model of the fouling process.

Correlation coefficients ranging from 0.81 to 0.987 were obtained in fitting the data to the model. No particular pattern was observed for delay times and they appeared not to have a significant influence on the asymptotic fouling resistance. The latter is a complex function of the alkalinity but generally increases with alkalinity for the conditions of the experiment. Scale strength appears to be a strong function of the non-calcium carbonate components of the scale.

On a étudié, sur une surface de transfert chauffée, le comportement relatif à la formation de tartre que présentait l'eau d'un tour de refroidissement simulée; l'alcalinité a été le principal paramètre considéré. Les courbes de l'encrassage versus le temps ont été adaptées à l'équation suivante:

  • equation image

qui avait été mise au point à partir d'un modèle simple du processus d'encrassage.

En adaptant les résultats au modèle, on a obtenu des coefficients de corrélation compris entre 0.81 et 0.987. On n'a observé aucune caractéristique particulière pour les temps de retard; ceux-ci ont paru n'avoir aucune influence importante sur la résistance à l'encrassage asymptotique. Ladite résistance est une fonction complexe de l'alcalinité, mais elle augmente généralement avec celle-ci dans les conditions de l'expérience. La résistance du tartre semble ětre une fonction importante des composants de celui-ci autres que le carbonate de calcium.