  • leaking ducts;
  • porous barrier;
  • ventilation;
  • auxiliary fan;
  • dead-end duct

Abstract

Analytic expressions for the flow and pressure in a dead-end duct which has loss of fluid through a porous wall are developed. The presence of an obstruction or auxiliary fan at the end of the duct is included. In either case there is a maximum permissible length of duct. As the duct length approaches this maximum, the main supply fan power and flow increase dramatically.

There is no recirculation within the duct when there is an obstruction at the end of the duct. If an auxiliary fan is used, there is always recirculation. However the use of an auxiliary fan can yield major savings in total power requirements.

On a développé des expressions analytiques pour I'écoulement et la pression et la pression dans un conduit en cul de sac encourant des pertes de fluide à travers une paroi poreuse. On a prévu la présence d'un obstacle ou d'un ventilateur secondaire à I'extrémité du conduit. Dans tous les cas, on observe I'existence d'une longueur maximale. Lorsqu'on approche du maximum permis, la puissance du ventilateur d'alimentation principale et I'écoulement augmentent considérablement.

Aucune recirculation n'est observée dans le conduit lorsqu'il existe un obstacle à son extrémité, mais on observe toujours une recirculation en présence d'un ventilateur secondaire. Cependant, I'utilisation d'un ventilateur secondaire peut entraêner des économies importantes dans les besoins en puissance.