The fire hazard of an ethanol process facility†
Article first published online: 6 OCT 2011
DOI: 10.1002/prs.10495
Copyright © 2011 American Institute of Chemical Engineers (AIChE)
Additional Information
How to Cite
Ditch, B. (2011), The fire hazard of an ethanol process facility. Proc. Safety Prog., 30: 365–371. doi: 10.1002/prs.10495
- †
Publication History
- Issue published online: 16 NOV 2011
- Article first published online: 6 OCT 2011
- Abstract
- Article
- References
- Cited By
Keywords:
- ethanol;
- hazard analysis;
- sprinkler protection
Abstract
A large release of high purity ethanol has been shown to pose a significant hazard to the structure and sensitive equipment of an unprotected process facility. A new methodology was developed that provides a practical means of measuring the maximum heat flux from an unprotected fire and the relative effectiveness of various water-based protection schemes. These results were combined with large-scale testing, using a representative multilevel process structure, to evaluate the performance of several sprinkler and water spray systems designs common to the industry. Several of these protection systems were shown to be inadequate to reduce the hazard below an acceptable level. However, when designed properly, sprinkler systems were shown to provide acceptable protection of the process structure, though local area water spray was needed for protecting objects near the pool fire surface. © 2011 American Institute of Chemical Engineers Process Saf Prog, 2011

1547-5913/asset/PRS_left.gif?v=1&s=eec397d21f5de7c3ba50a866c28a6ea0caff404d)
1547-5913/asset/olbannercenter.gif?v=1&s=f18d7f26479b19745893996bf9374eef1f4cad3c)
1547-5913/asset/PRS_right.gif?v=1&s=e540b85b3f450889df2a9637783b5c62856f00a0)