Use of visual CO2 feedback as a retrofit solution for improving classroom air quality

Authors

  • P. Wargocki,

    Corresponding author
    1. International Centre for Indoor Environment and Energy (ICIEE), DTU Civil Engineering, Technical University of Denmark (DTU), Lyngby, Denmark
    • P. Wargocki

      International Centre for Indoor Environment and Energy (ICIEE)

      DTU Civil Engineering

      Technical University of Denmark (DTU)

      Lyngby, Denmark

      Tel.: +45 45254011

      Fax: +45 45932166

      e-mail: paw@byg.dtu.dk

    Search for more papers by this author
  • N. A. F. Da Silva

    1. International Centre for Indoor Environment and Energy (ICIEE), DTU Civil Engineering, Technical University of Denmark (DTU), Lyngby, Denmark
    Search for more papers by this author

Abstract

Carbon dioxide (CO2) sensors that provide a visual indication were installed in classrooms during normal school operation. During 2-week periods, teachers and students were instructed to open the windows in response to the visual CO2 feedback in 1 week and open them, as they would normally do, without visual feedback, in the other week. In the heating season, two pairs of classrooms were monitored, one pair naturally and the other pair mechanically ventilated. In the cooling season, two pairs of naturally ventilated classrooms were monitored, one pair with split cooling in operation and the other pair with no cooling. Classrooms were matched by grade. Providing visual CO2 feedback reduced CO2 levels, as more windows were opened in this condition. This increased energy use for heating and reduced the cooling requirement in summertime. Split cooling reduced the frequency of window opening only when no visual CO2 feedback was present.